Thermosiphon

A thermosiphon transfers heat through gravity-driven fluid circulation, using temperature-related density differences rather than a mechanical pump.

18 keywords1 linked from3 not yet writtenWritten by AI
HeatGravityDensityHeat ExchangerEnergy BalanceTemperatureLatent HeatPressureThermosiph…

A thermosiphon is a device or circulation arrangement that transfers heat by allowing a fluid to move under the influence of gravity, without a mechanical circulation pump. Heating and cooling create differences in density that produce a driving pressure: denser fluid tends to descend while less-dense fluid rises. The term covers both single-phase circulation loops, in which the fluid remains liquid or gas, and two-phase devices, in which evaporation and condensation transport heat. Thermosiphons are used in water heating, industrial equipment, electronic cooling, and ground-temperature control.

Operating principle

Thermosiphon circulation is an engineered use of natural convection. In a typical liquid system, a heat source warms fluid in a lower section of a circuit. Under ordinary operating conditions, the warmed fluid becomes less dense and rises through one passage. A cooler, denser fluid column descends through another passage, completing the circuit.

The driving force is not simply that “heat rises.” Heat can be transferred in any direction; it is the gravitational response to unequal fluid densities that produces circulation. Fluid properties and the arrangement of the heating and cooling regions determine whether a particular layout will circulate.

For an idealized loop containing approximately uniform hot and cold vertical columns, the available driving pressure is

Δpdrive≈gH(ρc−ρh),\Delta p_{\mathrm{drive}} \approx gH(\rho_c-\rho_h),

where gg is gravitational acceleration, HH is the effective vertical height, and ρc\rho_c and ρh\rho_h are the densities of the cold and hot columns. In a real loop, density varies along the flow path, so the driving pressure depends on the complete density distribution.

At steady operation, the driving pressure balances friction and other flow losses:

Δpdrive=Δploss.\Delta p_{\mathrm{drive}}=\Delta p_{\mathrm{loss}}.

The resulting flow rate is therefore determined jointly by heat input, fluid properties, elevation, pipe dimensions, and resistance in valves, bends, and heat exchangers. Heating does not impose a fixed flow rate as a positive-displacement pump would.

For a single-phase liquid with approximately constant specific heat capacity, the transported heat rate can be written as

Q˙=m˙cp(Tout−Tin),\dot Q=\dot m c_p(T_{\mathrm{out}}-T_{\mathrm{in}}),

where m˙\dot m is mass flow rate and cpc_p is specific heat capacity. This relation is an energy balance, not a separate prediction of circulation rate.

Main types

Single-phase thermosiphons

In a single-phase thermosiphon, the working fluid does not boil or condense during normal operation. Water, water–glycol mixtures, oils, and gases can serve as working fluids, depending on the required temperature range and material compatibility.

A common arrangement places a heater or collector below a storage vessel or cooling section. Separate rising and descending passages maintain circulation. The loop need not be hermetically sealed: some systems connect to an open or vented reservoir, while others operate in closed, pressurized circuits.

Because the density difference between warm and cool liquid is often modest, these systems generally require low flow resistance and a favorable elevation difference. Trapped gas can interrupt circulation or substantially reduce it.

Two-phase thermosiphons

A two-phase thermosiphon uses evaporation at a heated surface and condensation at a cooler surface. Vapor moves toward the cooling region, and the condensate returns under gravity. Much of the transferred energy is carried as latent heat, allowing substantial heat transport with a relatively small temperature difference.

Two common configurations are:

  • Closed tubular thermosiphons: vapor travels upward through a tube while liquid returns downward along its inner wall.
  • Loop thermosiphons: separate vapor and liquid lines connect an evaporator and a condenser, reducing direct opposition between the two flows.

In their usual gravity-assisted arrangement, the condenser is above the evaporator. The working fluid and internal pressure establish the boiling and condensation temperatures.

A two-phase thermosiphon is closely related to a heat pipe. Conventional wicked heat pipes return liquid by capillary action and can operate against gravity within their design limits. A thermosiphon relies primarily on gravity for liquid return and generally has no wick. Terminology varies: a closed two-phase thermosiphon may also be described as a wickless heat pipe.

Distinction from siphons and heat pumps

Despite its name, a thermosiphon does not operate by the same mechanism as an ordinary siphon. A conventional siphon transfers liquid between different elevations through a continuous liquid column. A thermosiphon instead obtains its circulating pressure from differences in fluid density, normally maintained by heating and cooling.

It is also not a heat pump. A thermosiphon passively transfers heat from a hotter region to a colder one; it does not use a compressor or another work-driven cycle to raise heat from a colder source to a hotter sink. Eliminating a circulation pump does not eliminate the need for a temperature difference or a suitable heat-rejection environment.

Development and applications

Thermosiphon circulation became established in hot-water heating and engine cooling before small mechanical circulation pumps were widespread. Its later applications include compact two-phase devices, industrial heat exchange, and passive cooling systems.

Solar and domestic water heating

In solar-energy systems, a collector heats fluid that rises toward an elevated storage tank. Cooler fluid returns to the collector through a lower connection. The arrangement can circulate without electrical pumping, although its performance depends on sunlight, collector and tank geometry, and pipe resistance.

Some systems circulate potable water directly; others use a separate collector fluid and transfer heat through a heat exchanger. Freezing, mineral deposition, overheating, and heat loss through reverse circulation are important design considerations.

Thermosiphon circulation also occurs in certain stove-heated water systems and older gravity-fed central-heating installations.

Engines and industrial equipment

Some early internal combustion engines circulated coolant between the engine jacket and radiator by thermosiphon action. Pumped circulation later became prevalent because it supports more compact layouts and more controlled flow over a wide operating range.

In chemical engineering, thermosiphon reboilers use density differences between the return liquid and the heated, often partially vaporized stream to circulate process fluid through a heat exchanger. Their performance depends strongly on available liquid head, vapor generation, and piping resistance.

Natural circulation is also important in certain boilers and nuclear reactors. It can support normal heat transport or passive removal of residual heat, depending on the design. Passive circulation remains subject to limits imposed by coolant inventory, pressure losses, and the available heat sink.

Electronic and electrical cooling

Two-phase thermosiphons can transfer heat from electronic components or power equipment to a remotely positioned condenser. Separating the evaporator and condenser can provide more layout flexibility than placing cooling fins directly on the heat source.

The absence of a liquid circulation pump can reduce moving parts, but the complete cooling installation may still use fans or other powered equipment. Heat-removal capacity remains limited by boiling, condensate return, and condenser performance.

Ground-temperature control

Sealed thermosiphons are used to cool permafrost beneath or around structures. In a typical installation, a buried evaporator absorbs ground heat, while an above-ground condenser rejects it to colder outdoor air.

Such devices operate passively when the air is sufficiently colder than the ground. Their effectiveness therefore depends on seasonal conditions, soil properties, and thermal loads. Their gravity-return arrangement can strongly limit reverse heat transfer, but it does not eliminate all heat conduction through the device.

Performance limits and design considerations

The principal advantage of a thermosiphon is circulation without a mechanical pump. This can reduce pumping energy, noise, and maintenance associated with moving components. It does not make the system independent of installation conditions.

Important limitations include:

  • Orientation and elevation: insufficient height or an unfavorable arrangement can weaken or stop circulation.
  • Flow resistance: narrow passages, fouling, valves, and long pipe runs can consume the available driving pressure.
  • Startup and stability: weak initial density differences may delay startup; some boiling loops exhibit oscillation or flow reversal.
  • Two-phase flow limits: opposing vapor and liquid flows can cause flooding or entrainment. Inadequate liquid supply can leave the evaporator dry.
  • Fluid inventory and contamination: an unsuitable charge or non-condensable gas can impair heat transfer.
  • Materials and operating range: corrosion, freezing, thermal expansion, and internal pressure constrain fluid and enclosure selection.

Thermosiphon performance cannot be inferred from pipe size or heat input alone. It depends on the coupled behavior of heat transfer, fluid flow, phase change where present, and the external heat sink.