Evaporative Cooling

Evaporative cooling lowers temperature through the energy required for liquid evaporation or, in trapped gases, the selective removal of high-energy particles.

20 keywords4 linked from2 not yet writtenWritten by AI
TemperatureEvaporationPhase TransitionLatent HeatWaterHeat CapacityThermodynamic Eq…CondensationEvaporativ…

Evaporative cooling is the reduction of temperature caused by evaporation. When a liquid becomes vapor, it absorbs energy from the liquid itself and its surroundings, potentially cooling both. The process underlies sweating, cooling in porous water containers, many building-cooling systems, and industrial cooling towers. A related technique in atomic physics cools trapped gases by selectively removing energetic particles rather than by evaporating a bulk liquid.

Physical principles

Energy transfer during evaporation

Evaporation is a phase transition that occurs at a liquid’s surface and can take place below its boiling point. Molecules leaving the liquid must overcome attractive interactions with neighboring molecules. The energy associated with this transition is described by the latent heat of vaporization, commonly expressed as energy per unit mass.

For a steady evaporation rate, the thermal power absorbed in vaporization is approximately

Q˙evap=m˙evaphfg,\dot Q_{\mathrm{evap}}=\dot m_{\mathrm{evap}}h_{fg},

where m˙evap\dot m_{\mathrm{evap}} is the mass evaporated per unit time and hfgh_{fg} is the specific enthalpy of vaporization at the relevant temperature. For water near 25 ∘C25\,^\circ\mathrm{C}, hfgh_{fg} is about 2.442.44 megajoules per kilogram. Evaporating one kilogram per hour therefore absorbs roughly 680680 watts of thermal power.

This is not necessarily the net cooling delivered to a particular object. Some energy may come from the surrounding air, incoming liquid, sunlight, or other heat sources. The temperature change depends on the complete energy balance, including heat entering the system and its heat capacity.

At the molecular level, escaping particles carry away energy. Their removal, together with the energy needed to separate them from the liquid, can lower the average energy of the remaining material. Subsequent molecular interactions redistribute energy within it. Cooling continues only while evaporation removes energy faster than other processes replace it.

Vapor pressure and moisture transport

A liquid has an equilibrium vapor pressure that increases strongly with temperature. Net evaporation is favored when the vapor pressure of the surrounding gas is lower than the equilibrium value at the liquid surface. At thermodynamic equilibrium, evaporation and condensation balance, so there is no net evaporative cooling.

In practical equipment, evaporation also depends on transport through the air next to the wet surface. A simplified relation is

m˙evap≈kmA(ρv,s−ρv,∞),\dot m_{\mathrm{evap}} \approx k_m A\left(\rho_{v,s}-\rho_{v,\infty}\right),

where kmk_m is a mass-transfer coefficient, AA is the wetted area, and ρv,s\rho_{v,s} and ρv,∞\rho_{v,\infty} are the water-vapor densities at the surface and in the surrounding air. Airflow often increases evaporation by thinning the moist boundary layer and carrying vapor away.

Important operating factors therefore include:

  • Air humidity: dry air generally accepts more water vapor than humid air at the same temperature.
  • Air movement: ventilation replaces moisture-laden air with less humid air.
  • Wetted area: porous media, films, and droplets provide large surfaces for evaporation.
  • Water and air temperatures: these affect both vapor pressure and heat transfer.
  • Atmospheric pressure: this affects moist-air properties and the relationship between temperature and moisture content.

Wet-bulb temperature and cooling limits

The wet-bulb temperature is the temperature indicated by a wetted thermometer under specified ventilation and shielding conditions. It reflects a balance between heat transferred to the wet surface and energy removed by evaporation. The ordinary air temperature, measured without evaporative wetting, is called the dry-bulb temperature.

For an idealized, single-stage direct evaporative cooler operating approximately adiabatically with recirculated water, the incoming air’s thermodynamic wet-bulb temperature is the limiting outlet temperature. Real equipment normally delivers warmer air because contact time, wetted area, and heat transfer are finite.

A common performance measure is saturation effectiveness:

ε=Tdb,in−Tdb,outTdb,in−Twb,in,\varepsilon= \frac{T_{\mathrm{db,in}}-T_{\mathrm{db,out}}} {T_{\mathrm{db,in}}-T_{\mathrm{wb,in}}},

where Tdb,inT_{\mathrm{db,in}} and Tdb,outT_{\mathrm{db,out}} are inlet and outlet dry-bulb temperatures, and Twb,inT_{\mathrm{wb,in}} is the inlet wet-bulb temperature.

For example, air entering at 35 ∘C35\,^\circ\mathrm{C}, with a wet-bulb temperature of 20 ∘C20\,^\circ\mathrm{C}, would leave a cooler of effectiveness 0.800.80 at approximately

Tdb,out=35−0.80(35−20)=23 ∘C.T_{\mathrm{db,out}} =35-0.80(35-20) =23\,^\circ\mathrm{C}.

The difference between dry-bulb and wet-bulb temperatures is the wet-bulb depression. It is generally large in hot, dry conditions and small when relative humidity is high.

Direct evaporative cooling approximately follows a constant-moist-air-enthalpy path under common simplifying assumptions. The air’s sensible temperature decreases while its water-vapor content increases. Describing the process as an adiabatic process means that little heat crosses the external boundary of the air–water apparatus; it does not mean that heat transfer between air and water is absent.

Main engineering arrangements

Direct evaporative cooling

In a direct evaporative cooler, the air being supplied to a space contacts water, commonly through wetted pads or sprays. Some water evaporates into the air, lowering its dry-bulb temperature and increasing its moisture content.

Such systems generally use electricity for fans and pumps rather than a refrigerant compressor. Their performance depends strongly on local weather and on maintaining an airflow path through the building. They do not dehumidify incoming air, and their added moisture can limit suitability in humid climates or moisture-sensitive spaces.

Indirect and multistage cooling

Indirect evaporative cooling separates the supply air from a secondary air stream in which evaporation occurs. A heat exchanger transfers heat from the supply air to the evaporatively cooled side. Ideally, this cools the supply air without adding moisture to it.

Two-stage systems may combine indirect cooling with a direct stage. Regenerative designs use part of the cooled air as a working stream and can achieve supply temperatures below the original inlet wet-bulb temperature. This does not violate the single-stage limit, which applies to a different process arrangement. The attainable temperature depends on the flow configuration, heat exchanger, and working-air conditions.

Cooling towers and evaporative condensers

A cooling tower rejects heat from circulating water to the atmosphere through a combination of evaporation and sensible heat transfer. Only part of the water evaporates; the remaining water is cooled and recirculated. Applications include power generation, industrial processing, and building cooling systems.

An evaporative condenser combines evaporation with the condensation of a refrigerant or process vapor inside heat-transfer surfaces. Evaporative heat rejection can operate at lower temperatures than dry air cooling under suitable atmospheric conditions, but it consumes water and requires water management.

Natural and historical uses

Evaporation from skin transfers heat away from humans and many other animals. Sweat provides its principal cooling effect when it evaporates; liquid that drips away has not delivered the corresponding latent-heat cooling at the skin.

In plants, evaporation from internal leaf surfaces and the subsequent loss of vapor through stomata contribute to leaf cooling. Together with evaporation from soils and other surfaces, this forms evapotranspiration, an important part of the water cycle and surface energy balance. Water availability, wind, humidity, and stomatal behavior constrain the process.

Porous earthenware vessels have long exploited evaporation to cool stored water. Water reaching the outside surface evaporates and draws energy from the vessel and its contents. Wet textiles, wetted screens, and water features have likewise been used in traditional cooling practices. Mechanical fans, pumps, and manufactured wetted media later enabled more controlled building and industrial applications.

Evaporative cooling of atomic gases

In atomic physics, evaporative cooling usually means the selective removal of the most energetic atoms from a trap. Elastic collisions then redistribute energy among the remaining atoms, producing a lower temperature.

The process can be implemented by lowering a trap’s confining barrier or by using radio-frequency fields to remove atoms above a chosen energy threshold in a magnetic field trap. Unlike ordinary liquid evaporation, no liquid–vapor interface is required.

Forced evaporative cooling was central to the production of dilute-gas Bose–Einstein condensates in 1995 and remains important in ultracold-gas research. Its effectiveness depends on sufficiently rapid rethermalizing collisions and sufficiently low unwanted particle losses. Cooling sacrifices atom number, so temperature reduction must be balanced against loss of the trapped sample.

Constraints and environmental considerations

Evaporative systems exchange some electrical demand for water consumption. Their overall environmental performance depends on climate, water availability, equipment design, electricity supply, and the cooling system used for comparison. They are not uniformly preferable in every setting.

Evaporation leaves most dissolved minerals behind. Recirculating systems can therefore develop increasing salt concentrations, scale, corrosion, and deposits. Water discharged to control mineral concentration, known as blowdown, increases total water demand beyond the amount evaporated.

Equipment that stores or circulates water can support microbial growth. Systems that generate airborne droplets require particular attention because droplets can transport microorganisms; pure water vapor is distinct from these liquid aerosols.

Finally, evaporative cooling does not destroy energy. In accordance with the first law of thermodynamics, it transfers energy and redistributes it between sensible and latent forms. The heat removed from an object or air stream is carried into the surrounding environment, principally in the added water vapor and exhaust air.