{
  "id": "coefficient-of-performance",
  "title": "Coefficient of Performance",
  "lang": "en",
  "source_lang": "en",
  "summary": "The coefficient of performance measures useful heating or cooling delivered per unit of energy supplied to a thermal system.",
  "category": "technology",
  "subcategory": "engineering",
  "type": "concept",
  "aliases": [
    "COP",
    "Performance coefficient"
  ],
  "generated_at": "2026-11-05",
  "model": "pro/gpt-6.1-sol",
  "url": "https://aiwiki.page/en/coefficient-of-performance/",
  "translations": {
    "zh-Hans": {
      "url": "https://aiwiki.page/zh/coefficient-of-performance/",
      "json": "https://aiwiki.page/zh/coefficient-of-performance.json"
    }
  },
  "sections": [
    {
      "heading": "",
      "text": "The coefficient of performance (COP) is a dimensionless measure of the performance of a heat pump, refrigeration system, or air-conditioning system, defined as useful heating or cooling delivered divided by the energy supplied to operate it. Unlike the thermal efficiency of a heat engine, COP can exceed one because a heat pump transfers heat from a source to a destination rather than converting its input energy entirely into heat. A reported COP is meaningful only when the operating conditions, useful output, and boundaries of the measured system are specified."
    },
    {
      "heading": "Definition and energy balance",
      "text": "For a work-driven system, the heating coefficient of performance is\n\n\\[\\mathrm{COP}_{\\mathrm{H}}=\\frac{Q_{\\mathrm{H}}}{W},\\]\n\nwhere \\(Q_{\\mathrm{H}}\\) is the heat delivered to the warmer region and \\(W\\) is the work supplied over the same interval. The cooling coefficient of performance is\n\n\\[\\mathrm{COP}_{\\mathrm{C}}=\\frac{Q_{\\mathrm{C}}}{W},\\]\n\nwhere \\(Q_{\\mathrm{C}}\\) is the heat removed from the colder region.\n\nUnder steady operating conditions, these expressions can be written using rates:\n\n\\[\\mathrm{COP}_{\\mathrm{H}}=\\frac{\\dot Q_{\\mathrm{H}}}{P}, \\qquad \\mathrm{COP}_{\\mathrm{C}}=\\frac{\\dot Q_{\\mathrm{C}}}{P},\\]\n\nwhere heat-transfer rates and input power are expressed in compatible units, such as watts. COP therefore has no physical unit, although it is sometimes displayed as watts per watt.\n\nFor a cyclic device exchanging heat only with a hot region and a cold region, the energy balance gives\n\n\\[Q_{\\mathrm{H}}=Q_{\\mathrm{C}}+W.\\]\n\nConsequently,\n\n\\[\\mathrm{COP}_{\\mathrm{H}}=\\mathrm{COP}_{\\mathrm{C}}+1.\\]\n\nThis identity applies to the same device operating under the same conditions with consistent system boundaries. It does not generally relate the separately rated heating and cooling COPs of a reversible air conditioner, because those ratings usually use different operating conditions.\n\nExample\n\nA heat pump consumes \\(1\\ \\mathrm{kWh}\\) of electricity while extracting \\(3\\ \\mathrm{kWh}\\) of heat from its surroundings and delivering \\(4\\ \\mathrm{kWh}\\) indoors. Its heating COP is 4. For the same energy transfers, treating heat removal from the cold side as the useful output gives a cooling COP of 3.\n\nNo energy is created: the delivered heat includes both the extracted environmental heat and the supplied electrical energy. An electrical resistance heater, by comparison, has a point-of-use heating COP close to 1 when essentially all its electrical input becomes useful heat within the heated space."
    },
    {
      "heading": "Thermodynamic limits",
      "text": "The upper limit on COP follows from the second law of thermodynamics. For a reversible device operating between two reservoirs at constant absolute temperatures \\(T_{\\mathrm{H}}\\) and \\(T_{\\mathrm{C}}\\), with \\(T_{\\mathrm{H}}>T_{\\mathrm{C}}\\), the Carnot limits are\n\n\\[\\mathrm{COP}_{\\mathrm{H,Carnot}} = \\frac{T_{\\mathrm{H}}}{T_{\\mathrm{H}}-T_{\\mathrm{C}}},\\]\n\nand\n\n\\[\\mathrm{COP}_{\\mathrm{C,Carnot}} = \\frac{T_{\\mathrm{C}}}{T_{\\mathrm{H}}-T_{\\mathrm{C}}}.\\]\n\nBoth temperatures must be expressed on an absolute temperature scale, normally kelvin. Substituting Celsius temperatures directly into these equations gives incorrect results.\n\nThe temperature difference between the hot and cold sides is often called the temperature lift. A larger lift generally lowers the attainable COP. This explains why heating a building becomes more demanding when the outdoor heat source is colder or the required heating-water temperature is higher.\n\nFor ideal reservoirs at \\(0^\\circ\\mathrm{C}\\) and \\(35^\\circ\\mathrm{C}\\), the heating Carnot COP is approximately\n\n\\[\\frac{308.15}{308.15-273.15}\\approx 8.8.\\]\n\nAn actual system operating between those external conditions achieves a lower COP. Heat must cross finite temperature differences in each heat exchanger, while compression, fluid flow, and other processes introduce irreversibilities.\n\nThe ideal COP increases without bound as the reservoir temperature difference approaches zero. This mathematical limit does not imply unlimited useful heating or cooling from a finite practical machine: transferring heat at a finite rate requires adequate heat-transfer area and temperature differences."
    },
    {
      "heading": "Factors affecting actual performance",
      "text": "In vapor-compression refrigeration, COP depends on the refrigerant cycle, compressor performance, heat exchangers, controls, and operating conditions. Important influences include:\n\n- Source and delivery temperatures. Lower heating-delivery temperatures and warmer heat sources generally improve heating COP. Lower heat-rejection temperatures and higher acceptable cooling temperatures generally improve cooling COP.\n- Compressor and motor losses. Inefficient compression and losses in the electric motor increase input energy.\n- Heat-exchanger performance. Fouling, restricted airflow, and inadequate fluid flow can increase the temperature lift required within the refrigerant cycle.\n- Part-load operation. Variable-speed operation can improve performance under suitable conditions, while repeated starting and stopping introduces cycling losses.\n- Auxiliary electricity use. Fans, circulation pumps, controls, crankcase heaters, and standby functions may contribute to total consumption.\n- Frost and defrost. In air-source heating operation, frost can restrict airflow and heat transfer. Defrosting consumes energy and may temporarily reduce useful heat delivery.\n- Supplementary heating. Electrical resistance backup can reduce the overall COP of a heating installation even when the heat pump itself operates efficiently.\n\nSystems using ground-source heat often encounter more stable source temperatures than air-source systems, but their overall performance also depends on circulation energy and the design of the ground heat exchanger."
    },
    {
      "heading": "Equipment COP and system COP",
      "text": "A compressor-only COP, a complete-unit COP, and an installed-system COP can differ substantially. Each uses a different boundary for counting energy inputs and useful outputs.\n\nFor example, a laboratory equipment rating may include specified fan or pump allowances but exclude some external distribution equipment. A building-level measurement may include circulation pumps, backup heaters, and heat losses between the heat pump and occupied rooms. Comparisons require the same boundary or an explicit adjustment for those differences.\n\nWhere useful heat is measured from a flowing liquid, its rate is commonly estimated as\n\n\\[\\dot Q=\\dot m c_p\\Delta T,\\]\n\nwhere \\(\\dot m\\) is mass flow rate, \\(c_p\\) is specific heat capacity, and \\(\\Delta T\\) is the measured fluid temperature change. This approximation is appropriate when the fluid remains in a single phase and its properties are sufficiently constant. More generally, heat transfer is calculated from mass flow and the enthalpy difference.\n\nErrors in temperature, flow, and electrical-power measurements contribute to measurement uncertainty in the calculated COP. Small measured temperature differences can make relative errors especially significant."
    },
    {
      "heading": "Seasonal performance and related ratings",
      "text": "An instantaneous or test-point COP describes performance at particular conditions. It does not by itself establish annual energy consumption.\n\nA seasonal performance factor is based on total useful heat or cooling and total input energy over a defined period:\n\n\\[\\mathrm{SPF} = \\frac{\\int \\dot Q_{\\mathrm{useful}}\\,dt} {\\int P_{\\mathrm{input}}\\,dt}.\\]\n\nThis is a ratio of accumulated energies, not the ordinary arithmetic mean of individual COP readings. Seasonal measures can account for changing weather, part-load operation, defrosting, standby consumption, and backup heating, depending on their definitions.\n\nRelated ratings include seasonal COP, seasonal energy efficiency ratio, and heating seasonal performance factor. Their test procedures, units, and treatment of auxiliaries vary by standard and jurisdiction, so their numerical values are not automatically interchangeable.\n\nThe energy efficiency ratio (EER) is another cooling-performance measure. When EER is expressed in British thermal units per hour per watt,\n\n\\[\\mathrm{EER}\\approx 3.412\\,\\mathrm{COP}_{\\mathrm{C}}.\\]\n\nIn conventions where EER is expressed in watts per watt, it is numerically equal to cooling COP."
    },
    {
      "heading": "Heat-driven systems",
      "text": "In absorption refrigeration, the principal driving input is heat rather than mechanical work. A thermal cooling COP is commonly defined as\n\n\\[\\mathrm{COP}_{\\mathrm{thermal}} = \\frac{Q_{\\mathrm{C}}}{Q_{\\mathrm{drive}}},\\]\n\nwhere \\(Q_{\\mathrm{drive}}\\) is the heat supplied to the generator. Pump electricity and other auxiliary inputs may be reported separately or included under a stated accounting method.\n\nA thermal COP and an electrically driven COP are not directly equivalent measures of resource use. Heat and electricity have different capacities to perform work, and the significance of the input depends on its source. Waste heat, heat from solar energy, and heat produced by burning fuel can have different economic and environmental implications even at the same thermal COP."
    },
    {
      "heading": "Interpretation and limitations",
      "text": "COP measures thermal output relative to a specified energy input; it does not directly measure cost, emissions, or total resource consumption. Those assessments also depend on energy prices, fuel use, the generation mix of the electrical grid, and the chosen accounting boundaries.\n\nA high COP likewise does not necessarily imply low total energy demand. A large heating or cooling load can require substantial input energy even when the equipment performs well. Conversely, reducing the load can lower consumption without changing the equipment’s rated COP.\n\nWhere heating and cooling are simultaneously useful, both outputs may be counted in a clearly defined combined performance measure. Such a measure is distinct from conventional heating-only or cooling-only COP and requires both outputs to serve actual demands."
    }
  ],
  "links": [
    "heat-pump",
    "refrigeration",
    "air-conditioning",
    "heat-engine",
    "heat",
    "energy-balance",
    "thermodynamics",
    "temperature",
    "heat-exchanger",
    "vapor-compression-refrigeration",
    "electric-motor",
    "geothermal-energy",
    "measurement-uncertainty",
    "solar-energy",
    "electrical-grid"
  ],
  "sources": [],
  "license": "https://creativecommons.org/licenses/by/4.0/"
}